In order to promote public education and public safety, equal justice for all, a better informed citizenry, the rule of law, world trade and world peace, this legal document is hereby made available on a noncommercial basis, as it is the right of all humans to know and speak the laws that govern them.

END OF PREAMBLE (NOT PART OF THE STANDARD)

EUROPEAN STANDARD
NORME EUROPÉENNE
EUROPÄlSCHE NORM

EN 1996-3

January 2006

ICS 91.010.30; 91.080.30

Supersedes ENV 1996-3:1999
Incorporating corrigendum October 2009

English Version

Eurocode 6 - Design of masonry structures - Part 3: Simplified calculation methods for unreinforced masonry structures

Eurocode 6 - Calcul des ouvrages en maçonnerie - Partie 3: Méthodes de calcul simplifiées pour les ouvrages en maçonnerie non armeé Eurocode 6 - Bemessung und Konstruktion von Mauerwerksbauten - Teil 3: Vereinfachte Berechnungsmethoden für unbewehrte Mauerwerksbauten

This European Standard was approved by CEN on 24 November 2005.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Image

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2006 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members.

Ref. No. EN 1996-3:2006: E

1

Contents

Background of the Eurocode programme 4
Status and field of application of Eurocodes 5
National Standards implementing Eurocodes 6
Links between Eurocodes and harmonised technical specifications (ENs and ETAs) for products 6
National Annex for EN 1996-3 7
1 General 8
  1.1 Scope Part 3 of Eurocode 6 8
  1.2 Normative references 8
  1.3 Assumptions 8
  1.4 Distinction between Principles and Application Rules 8
  1.5 Definitions 9
    1.5.2 General 9
    1.5.2 Masonry 9
  1.6 Symbols 9
2 Basis of design 10
  2.1 General 10
  2.2 Basic variables 10
  2.3 Verification by the partial factor method 10
3 Materials 11
  3.1 General 11
  3.2 Characteristic compressive strength of masonry 11
  3.3 Characteristic flexural strength of masonry 11
  3.4 Characteristic initial shear strength of masonry 11
4 Design of unreinforced masonry walls using simplified calculation methods 12
  4.1 General 12
  4.2 Simplified calculation method for walls subjected to vertical and wind loading 12
    4.2.1 Conditions for application 12
    4.2.2 Determination of design vertical load resistance of a wall 15
  4.3 Simplified calculation method for walls subjected to concentrated loads 18
  4.4 Simplified calculation method for shear walls 19
    4.4.1 Verification of shear resistance of walls 19
    4.4.2 Design shear resistance 20
  4.5 Simplified calculation method for basement walls subject to lateral earth pressure 21
  4.6 Simplified calculation method for the design of walls subjected to limited lateral load but no vertical loads 22
  4.7 Simplified calculation method for the design of walls subjected to uniform lateral load but no vertical loads 22 2
Annex A (Informative) Simplified calculation method for unreinforced masonry walls of buildings not greater than 3 storeys 23
Annex B (Normative) Simplified calculation method for the design of internal walls not subject to vertical loads and with limited lateral load 26
Annex C (Informative) Simplified calculation method for the design of walls subjected to uniform lateral design load and no vertical loads 30
Annex D (Normative) Simplified method of determining the characteristic strength of masonry 35
3

Foreword

This European Standard EN 1996-3 has been prepared by Technical Committee CEN/TC 250 “Structural Eurocodes”, the secretariat of which is held by BSI.

This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by July 2006, and conflicting national standards shall be withdrawn at the latest by March 2010.

CEN/TC 250 is responsible for all Structural Eurocodes.

This document supersedes ENV 1996-3:1999

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Background of the Eurocode programme

In 1975, the Commission of the European Community decided on an action programme in the field of construction, based on article 95 of the Treaty. The objective of the programme was the elimination of technical obstacles to trade and the hannonisation of technical specifications.

Within this action programme, the Commission took the initiative to establish a set of harmonised technical rules for the design of construction works which, in a first stage, would serve as an alternative to the national rules in force in the Member States and, ultimately, would replace them.

For fifteen years, the Commission, with the help of a Steering Committee with Representatives of Member States, conducted the development of the Eurocodes programme, which led to the first generation of European codes in the 1980s.

In 1989, the Commission and the Member States of the EU and EFTA decided, on the basis of an agreement1 between the Commission and CEN, to transfer the preparation and the publication of the Eurocodes to the CEN through a series of Mandates, in order to provide them with a future status of European Standard (EN). This links de facto the Eurocodes with the provisions of all the Council’s Directives and/or Commission’s Decisions dealing with European standards (e.g. the Council Directive 89/106/EEC on construction products -CPD- and Council Directives 93/37/EEC, 92/50/EEC and 89/440/EEC on public works and services and equivalent EFTA Directives initiated in pursuit of setting up the internal market). The Structural Eurocode programme comprises the following standards generally consisting of a number of Parts:

1 Agreement between the Commission of the European Communities and the European Committee for Standardisation (CEN) concerning the work on Eurocodes for the design of building and civil engineering works (BC/CEN/03/89).

4

EN 1990, Eurocode: Basis of structural design.

EN 1991, Eurocode 1: Actions on structures.

EN 1992, Eurocode 2: Design of concrete structures.

EN 1993, Eurocode 3: Design of steel structures.

EN 1994, Eurocode 4: Design of composite steel and concrete structures.

EN 1995, Eurocode 5: Design of timber structures.

EN 1996, Eurocode 6: Design of masonry structures.

EN 1997, Eurocode 7: Geotechnical design.

EN 1998, Eurocode 8: Design of structures for earthquake resistance.

EN 1999, Eurocode 9: Design of aluminium structures.

Eurocode standards recognise the responsibility of regulatory authorities in each Member State and have safeguarded their right to determine values related to regulatory safety matters at national level where these continue to vary from State to State.

Status and field of application of Eurocodes

The Member States of the EU and EFTA recognise that Eurocodes serve as reference documents for the following purposes:

The Eurocodes, as far as they concern the construction works themselves, have a direct relationship with the Interpretative Documents2 referred to in Article 12 of the CPD, although they are of a different nature from harmonised product standards3. Therefore, technical aspects arising from the

2 According to Article 3.3 of the CPD, the essential requirements (ERs) shall be given concrete form in interpretative documents for the creation of the necessary links between the essential requirements and the mandates for harmonised ENs and ETAGs/ETAs.

3 According to Article 12 of the CPD the interpretative documents shall:

  1. give concrete form to the essential requirements by harmonising the terminology and the technical bases and indicating classes or levels for each requirement where necessary;
  2. indicate methods of correlating these classes or levels of requirement with the technical specifications, e.g. methods of calculation and of proof, technical rules for project design, etc.;
5

Eurocodes work need to be adequately considered by CEN Technical Committees and/or EOTA Working Groups working on product standards with a view to achieving full compatibility of these technical specifications with the Eurocodes.

The Eurocode standards provide common structural design rules for everyday use for the design of whole structures and component products of both a traditional and an innovative nature. Unusual forms of construction or design conditions are not specifically covered and additional expert consideration will be required by the designer in such cases.

National Standards implementing Eurocodes

The National Standards implementing Eurocodes will comprise the full text of the Eurocode (including any annexes), as published by CEN, which may be preceded by a National title page and National foreword, and may be followed by a National Annex (informative).

The National Annex may only contain information on those parameters which are left open in the Eurocode for national choice, known as Nationally Determined Parameters, to be used for the design of buildings and civil engineering works to be constructed in the country concerned, i.e.:

Links between Eurocodes and harmonised technical specifications (ENs and ETAs) for products.

There is a need for consistency between the harmonised technical specifications for construction products and the technical rules for works4. Furthermore, all the information accompanying the CE Marking of the construction products which refer to Eurocodes shall clearly mention which Nationally Determined Parameters have been taken into account.

This European Standard is part of EN 1996 which comprises the following parts:

Part 1-1: General rules for reinforced and unreinforced masonry.

  1. serve as a reference for the establishment of harmonised standards and guidelines for European technical approvals. The Eurocodes, de facto, play a similar role in the field of the ER 1 and a part of ER 2.

4 See Article 3.3 and Article 12 of the CPD, as well as clauses 4.2, 4.3.1, 4.3.2 and 5.2 of ID 1.

6

Part 1-2: General rules - Structural fire design.

Part 2: Design considerations, selection of materials and execution of masonry.

Part 3: Simplified calculation methods for unreinforced masonry structures.

EN 1996-1-1 describes the principles and requirements for safety, serviceability and durability of masonry structures. It is based on the limit state concept used in conjunction with a partial factor method. This EN 1996-3 describes simplified calculation methods to facilitate the design of unreinforced masonry walls based on the principles from EN 1996-1-1.

For the design of new structures, EN 1996 is intended to be used, for direct application, together with ENs 1990, 1991, 1992, 1993, 1994, 1995, 1997, 1998 and 1999.

EN 1996-3 is intended for use by:

National Annex for EN 1996-3

This standard gives some symbols for which a National value needs to be given, with notes indicating where national choices may have to be made. Therefore the National Standard implementing EN 1996-3 should have a National Annex containing all Nationally Determined Parameters to be used for the design of buildings and civil engineering works to be constructed in the relevant country.

National choice is allowed in EN 1996-3 through clauses:

7

1 General

1.1 Scope Part 3 of Eurocode 6

  1. P The scope of Eurocode 6 for Masonry Structures as given in 1.1.1 of EN 1996-1-1:2005 applies also to this EN 1996-3.

    NOTE: Eurocode 6 deals only with the requirements for resistance, serviceability and durability of structures. Other requirements are not considered. Eurocode 6 does not cover the special requirements of seismic design.

  2. P EN 1996-3 provides simplified calculation methods to facilitate the design of the following unreinforced masonry walls, subject to certain conditions of application:
  3. P The rules given in EN 1996-3 are consistent with those given in EN 1996-1-1, but are more conservative in respect of the conditions and limitations of their use.
  4. For those types of masonry structure or parts of structures not covered by (1), the design shall be based on EN 1996-1-1.
  5. This EN 1996-3 applies only to those masonry structures, or parts thereof, that are described in EN 1996-1-1 and EN 1996-2.
  6. The simplified calculation methods given in this EN 1996-3 do not cover the design for accidental situations.

1.2 Normative references

  1. P The references in 1.2 of EN 1996-1-1:2005 apply to this EN 1996-3.

1.3 Assumptions

  1. P The assumptions given in 1.3 of EN 1990:2002 apply to this EN 1996-3.

1.4 Distinction between Principles and Application Rules

  1. P The rules of 1.4 of EN 1990:2002 apply to this EN 1996-3.
8

1.5 Definitions

1.5.1 General

  1. The terms and definitions given in 1.5 of EN 1990:2002 apply to this EN 1996-3.
  2. The terms and definitions in 1.5 of EN 1996-1-1:2005 apply to this EN 1996-3.
  3. Additional terms and definitions used in this EN 1996-2 are given the meanings contained in clause 1.5.2.

1.5.2 Masonry

1.5.2.1
basement wall

a retaining wall constructed partly or fully below ground level.

1.6 Symbols

  1. P Material-independent symbols are given in 1.6 of EN 1990.
  2. P For the purpose of this standard the symbols given in EN 1996-1-1 apply.
  3. P Other symbols used in this EN 1996-3 are:
    bc is the distance apart of cross walls or other buttressing elements;
    c is a constant;
    fk,s is the characteristic compressive strength of masonry, determined from a simplified method;
    fvdo is the design value of the initial shear strength;
    fvdu is the design value of the limit to the shear strength;
    ha is the average height of the building;
    he is the height of the wall under ground level
    hm is the maximum height of a building allowed with the simplified calculation method;
    kG is a constant;
    l is the length of a wall in the horizontal direction;
    lbx is the plan dimension of a building in the x-direction;
    lby is the plan dimension of a building in the y-direction;
    lf is the span of a floor;
    lf,cf is the effective span of a floor;
    lsx is the length of a shear wall orientated in the x-direction;
    lsy is the length of a shear wall orientated in the y-direction; 9
    NEd,max is the design value of the maximum vertical load
    NEd,min is the design value of the minimum vertical load
    qEwd is the design wind load per unit area;
    wEk is the characteristic wind load per unit area;
    α is the loading ratio;
    β is a constant;
    ρe is the weight per volume of the soil;
    Φs is the capacity reduction factor.

2 Basis of design

2.1 General

  1. P The design of masonry buildings shall be in accordance with the general rules given in EN 1990.
  2. P Specific provisions for masonry structures are given in section 2 of EN 1996-1-1:2005 and shall be applied.

2.2 Basic variables

  1. P Actions shall be obtained from the relevant parts of EN 1991.
  2. P Partial factors for load shall be obtained from EN 1990.
  3. P Properties for materials and construction products and geometrical data to be used for design shall be those specified in EN 1996-1-1, or other relevant hENs of ETAs, unless otherwise indicated in this EN 1996-3.

2.3 Verification by the partial factor method

  1. P The verification by the partial factor method shall be done according to clause 2.4 of EN 1996-1-1:2005.

    NOTE: The notes to 2.4.2 of EN 1996-1-1:2005 also apply.

  2. P The relevant values of the partial factor for materials γM shall be used for the ultimate limit state for ordinary situations.

    NOTE: The numerical values to be ascribed to the symbol γM may be found in the National Annex. Recommended values are those as given in clause 2.4.3 of EN 1996-1-1:2005. The recommended values for masonry are repeated in the table below.

10
Material γM
Class
Masonry made with 1 2 3 4 5
Units of category I, designed mortar 1,5 1,7 2,0 2,2 2,5
Units of category I, prescribed mortar 1,7 2,0 2,2 2,5 2,7
Units of category II 2,0 2,2 2,5 2,7 3,0

END of NOTE

3 Materials

3.1 General

  1. P The materials used in the masonry walls referred to in this EN 1996-3 shall be in accordance with Section 3 of EN 1996-1-1:2005.
  2. Masonry units should be grouped as Group 1, Group 2, Group 3 or Group 4 according to clause 3.1.1 of EN 1996-1-1:2005.

    NOTE: Normally the manufacturer will state the grouping of his units in his product declaration.

3.2 Characteristic compressive strength of masonry

  1. The characteristic compressive strength of masonry should be determined according to 3.6.1 of EN 1996-1-1:2005.
  2. A simplified method to determine the characteristic compressive strength of masonry for use in this document is provided in Annex D.

3.3 Characteristic flexural strength of masonry

  1. The characteristic flexural strength of masonry should be determined according to 3.6.3 of EN 1996-1-1:2005.
  2. A simplified method to determine the characteristic flexural strengths of masonry for use in this document is provided in Annex D.

3.4 Characteristic initial shear strength of masonry

  1. The characteristic initial shear strength of masonry, fvko, should be determined according to 3.6.2 of EN 1996-1-1:2005. 11
  2. A simplified method to determine the characteristic initial shear strength of masonry for use in this document is provided in Annex D.

4 Design of unreinforced masonry walls using simplified calculation methods

4.1 General

  1. P The overall stability of a building, of which the wall forms a part, shall be verified.

    NOTE: The verification may be carried out in accordance with 5.4(1) of EN 1996-1-1:2005 or from a simplified method, which may be given in the National Annex.

4.2 Simplified calculation method for walls subjected to vertical and wind loading

4.2.1 Conditions for application

4.2.1.1 General conditions
  1. P For use of the simplified method the following conditions shall be complied with:
4.2.1.2 Additional conditions
  1. For walls acting as end supports to floors (see Figure 4.2), the simplified calculation method given in 4.2.2 may be applied only if the floor span lf is not greater than:

    7,0 m when NEdkG t b fd       (4.1a)

    or

    the lesser of 4,5 + 10 t (in m) and 7,0 m when fd > 2,5 N/mm2       (4.1b)

    or

    the lesser of 4,5 + 10 t (in m) and 6,0 m when fd ≤ 2,5 N/mm2       (4.1c)

    where:

    NEd is the design vertical load on the level being considered;
    t is the actual thickness of the wall, or the load bearing leaf of a cavity wall, acting as an end support, in metres;
    b is the width over which the vertical load is effective;
    fd is the design compressive strength of the masonry;
    kG is 0,2 for Group 1 masonry units
    is 0,1 for Group 2, Group 3 and Group 4 masonry units.
    13

    Figure 4.2 – Wall acting end support

    Figure 4.2 – Wall acting end support

  2. P Walls acting as end supports to floors or roofs that are subjected to wind loading shall be designed according to 4.2.2 only if:

    Image

    where:

    h is the clear storey height;
    qEwd is the design wind load on the wall per unit area of the wall;
    NEd is the design value of the vertical load giving the least severe effect on the wall at the top of the storey considered;
    b is the width over which the vertical load is effective;
    t is the actual thickness of the wall, or the load bearing leaf of a cavity wall, acting as an end support;
    α is Image
    c1, c2 are constants derived from Table 4.1.
    Table 4.1 : Constants c1 and c2
    α c1 c2
    0,05 0.12 0,017
    0,10 0,12 0,019
    0,20 0,14 0,022
    0,30 0,15 0,025
    0,50 0,23 0,031
    NOTE Linear interpolation is permitted.
    14

    NOTE Annex C gives a simplified method for lateral load design, but it may be used to obtain the thickness t instead of equation (4.2) if the design vertical load giving the most severe effect is Image kG b t fd or less, where kG Image, b, t and fd are as described in 4.2.1.2.

4.2.2 Determination of design vertical load resistance of a wall

4.2.2.1 General
  1. P Under the ultimate limit state it shall be vertical that:

    NEdNRd       (4.3)

    Where

    NEd is the design vertical load on the wall;
    NRd is the design design vertical load resistance of the wall according to clause 4.2.2.2.
4.2.2.2 Design vertical load resistance
  1. The design vertical load resistance NRd may be determined from:

    NRd = Φs fd A       (4.4)

    Where

    Φs is the capacity reduction factor allowing for the effects of slenderness and eccentricity of the loading, obtain from 4.2.2.3;
    fd is the design compressive strength of the masonry;
    A is the loaded horizontal gross sectional area of the wall.
4.2.2.3 Capacity reduction factor
  1. The capacity reduction factor Φs for intermediate walls should be determined from the equation (4.5a).

    Image

    For walls acting as end supports to the floors Φs should be determined from the lesser of equation (4.5a) or

    Image

    For walls at the highest level acting as end support to the top floor or roof Φs should be determined from the lesser of equations (4.5a), (4.5b) or

    Φs = 0,4       (4.5c)

    15

    where

    hef is the effective height of the wall (see 4.2.2 A);
    tef is the effective thickness determined in accordance with 5.5.1.3 of EN 1996-1-1:2005 or
    tef = t for a single leaf wall
    Image for a cavity wall with wall ties of not less than ntmin, the minimum number of wall ties per m2, where t1 and t2 are the actual thicknesses of the leaves and where the modulus of elasticity of the unloaded leaf is equal to or greater than 90% of that of the loaded leaf.
    lf,ef is the effective span of the floor in metres for which the wall is acting as end support, as follows:
    lf,ef = lf for simply supported floor structures;
    lf,ef = 0,7 lf for continuous floor structures;
    lf,ef = 0,7 lf for simply supported floors spanning in 2 directions where the supported length on the considered wall is not greater than two times lf;
    lf,ef = 0,5 lf for continuous floors spanning in 2 directions where the supported length on the considered wall is not greater than two times lf;
    Φs is the capacity reduction factor which incorporates the buckling effect, the initial eccentricity, the eccentricity due to loads and the creep effect.

    NOTE The value of ntmin for use in a country may be found in its National Annex; the recommended value is 2.

4.2.2.4 Effective height of walls
  1. The effective height may be determined by

    hef = ρn h      (4.6)

    where:

    h is the clear storey height;
    ρn is a reduction factor where n = 2, 3 or 4 depending on the edge restraint or stiffening of the wall.
  2. The reduction factor ρn may be determined as follows.
    1. For walls laterally and rotationally restrained, at top and bottom only, by reinforced or prestressed concrete floors or roofs (see Figure 4.3) and having a bearing of at least 2/3 the thickness of the wall, but not less than 85 mm:

      ρ2 = 1,0 if the wall is acting as end support to a floor,

      ρ2 = 0,75    for all other walls.

      16

      Figure 4.3 – Rotational restraint provided by floors or roof

      Figure 4.3 – Rotational restraint provided by floors or roof

    2. For all walls laterally restrained at top and bottom only (e.g. by ring beams of appropriate stiffness or timber floors) but not rotationally restrained by the floors or roof (see Figure 4.4):

      Figure 4.4 — No rotational restraint provided by floors or roof

      Figure 4.4 — No rotational restraint provided by floors or roof

    3. For walls laterally restrained at top and bottom and at one vertical edge (see figure 4.5):
      Image in the case of rotational restraint at top and bottom only as in (i) above if the wall is not acting as end support of the floor;
      ≤ 1,0 in all other cases in (i) and (ii) above

      where:

      h is the clear storey height;
      l is the distance from the vertically supported edge to the free edge.
      17

      Figure 4.5 – Wall laterally restrained at top and bottom and at one vertical edge

      Figure 4.5 – Wall laterally restrained at top and bottom and at one vertical edge

    4. For walls laterally restrained at top and bottom and at two vertical edges (see Figure 4.6):
      Image in the case of rotational restraint at top and bottom only as in (i) above if the wall is not acting as end support of the floor;
      ≤ 1,0 in all other cases in (i) and (ii) above

      where

      h is the clear storey height;
      l is the distance between the supports at the vertical edges

      Figure 4.6 – Wall laterally restrained at top and bottom and two vertical edges

      Figure 4.6 – Wall laterally restrained at top and bottom and two vertical edges

4.2.2.5 Slenderness ratio of walls
  1. The slenderness ratio of a wall hef/tef should not be greater than 27.

4.3 Simplified calculation method for walls subjected to concentrated loads

  1. The design value of the vertical concentrated load resistance of a wall, NRdc,may be obtained from:

    Image but not greater than 1,5 fd Ab       (4.7)

    18

    NRdc = fd Ab       (4.8)

    where:

    a1 is the distance from the end of the wall to the nearest edge of the bearing area of the concentrated load (see figure 4.7);
    hc is the height of the wall from the floor to the level of the load (see figure 4.7);
    Ab is the loaded area.

    Figure 4.7 – Elevation of wall with a concentrated load, in relation to a and hc

    Figure 4.7 – Elevation of wall with a concentrated load, in relation to a\ and hc

    provided that:

4.4 Simplified calculation method for shear walls

4.4.1 Verification of shear resistance of walls

  1. P Under the ultimate limit state, it shall be verified that:

    VEdVRd      (4.9)

    where :

    VEd is the design shear load on the wall,
    VRd is the design shear resistance of the wall.

    NOTE A further simplified calculation method of designing shear walls for buildings not exceeding 3 storeys in height is given in Annex A3.

19

4.4.2 Design shear resistance

  1. The design shear resistance VRd of a rectangular section may be determined as follows:

    Image

    where:

    cv is 3 for masonry with filled perpend joints or
    1,5 for masonry with unfilled perpend joints;
    l is the length of the wall in the bending direction;
    eEd is the eccentricity of the compressive load in the cross section being considered

    Image

    not taken less than Image

    MEd is the design value of the moment in the cross section being considered;
    NEd is the design value of the compressive load in the cross section being considered;
    t is the thickness of the wall;
    fvdo is the design value of the initial shear strength equal to fvko, according to 3.4, divided by γM;
    fvdu is the design value of the limit to the shear strength according to 3.6.2(3) and 3.6.2(4) of EN 1996-1-1:2005.

    NOTE The values of the limit to the shear strength can be found in EN 1996-1-1:2005.

  2. Equation (4.10a) may be used when:
20

4.5 Simplified calculation method for basement walls subject to lateral earth pressure

  1. The following simplified method may be used for designing basement walls subject to lateral earth pressure providing the following conditions are fulfilled:

    NOTE For the verification of the shear action due to earth pressure a coefficient of friction of 0,6 has been used.

  2. The design of the wall may be derived on the basis of the following expressions, as appropriate:

    Image

    Image

    where:

    NEd,max is the design value of the vertical load on the wall giving the most severe effect at the mid-height of the fill;
    NEd,min is the design value of the the vertical load on the wall giving the least severe effect at the mid-height of the fill;
    b is the width of the wall;
    bc is the distance apart of cross walls or other buttressing elements;
    h is the clear height of the basement wall;
    he is the height of the wall under ground level;
    t is the wall thickness; 21
    ρc is the weight per cubic metre of the soil;
    fd is the design compressive strength of the masonry;
    β is 20 when bc ≥ 2h,

    is 60 - 20 bc / h when h < bc < 2h,

    is 40 when bch.

Figure 4.8 – Variables for basement walls shown in cross section and plan

Figure 4.8 – Variables for basement walls shown in cross section and plan

4.6 Simplified calculation method for the design of walls subjected to limited lateral load but no vertical loads

  1. A Simplified calculation method for determining the minimum thickness an limiting dimension of internal walls, not subjected to vertical loads other than self-weight, but having variable conditions of lateral restraint, conditional on certain restrictions, is given in Annex B for walls with a limited lateral load.

4.7 Simplified calculation method for the design of walls subjected to uniform lateral load but no vertical loads

  1. Walls subjected to uniform lateral loads may be designed by a simplified method.

    NOTE A simplified calculation method for determining the minimum thickness and limiting dimensions of walls having variable conditions of lateral restraint and not subject to vertical to loads other self-weight is given in Annex C for walls subject to a uniform lateral design load.

22

Annex A
Simplified calculation method for unreinforced masonry walls of buildings not greater than 3 storeys

(Informative)

A.1 General conditions for application

  1. For buildings the simplified calculation method given in this annex may be used, provided the following conditions are fulfilled.

    where:

    hef is the effective height of the wall in accordance with 4.2.2.4;
    tef is the effective thickness determined in accordance with 4.2.2.3.

A.2 Design vertical load resistance of the wall

  1. The design vertical load resistance NRd is given by:

    NRd = cA fd A       (A.1)

    where:

    23
    cA = 0,50    if hef/tef ≤ 18

    = 0,36    hef/tef > 18 and ≤ 21;

    fd is the design compressive strength of the masonry;
    A is the loaded horizontal gross cross-sectional area of the wall, excluding any openings.

A.3 Shear walls without verification of wind load resistance

  1. Shear walls may be designed without verification of the wind load resistance, if the arrangement of shear walls is sufficient to stiffen the building against horizontal forces in two perpendicular directions.
  2. The arrangement of shear walls may be presumed to be sufficient if:

    where:

    lbx, lby are the plan dimensions of the building considered where lbxlby
    lsx, lsy are the shear wall lengths (see Figure A.1 and Figure A.2);
    htot is the height of the building;
    Cs = Ct Ci wEk;
    Ct is a constant depending on a, obtained from Table A.1, in m2/kN;
    Ci = 1,0 for rectangular shear walls

    = 0,67 for I-profiled shear walls with flange areas greater than 0,4 t l (see Figure Al);

    α is the average of the ratio Image of the shear walls being considered; 24
    NEd is the design value of the vertical load in a shear wall;
    A is the cross-sectional area of a shear wall;
    fd is the design compressive strength of the masonry;
    wEk is the characteristic wind load, in kN/m2.
    Table A.1 - Values of ct [ m2/kN]
    α fk [N/mm2]
    2 4 6 ≥8
    0,2 0,0192 0,0095 0,0064 0,0048
    0,3 0,0128 0,0064 0,0042 0,0032
    0,4 0,0095 0,0048 0,0032 0,0024
    0,5 0,0075 0,0038 0,0025 0,0019
    0,6 0,0095 0,0048 0,0032 0,0024
    0,7 0,0128 0,0064 0,0042 0,0032

    NOTE Linear interpolation is permitted.

    Figure A.1 – Plan of shear walls and requirement for 1-shapes

    Figure A.1 – Plan of shear walls and requirement for 1-shapes

    Figure A.2 – Layout of shear walls

    Figure A.2 – Layout of shear walls

25

Annex B
Simplified calculation method for the design of internal walls not subject to vertical loads and with limited lateral load

(Normative)

  1. Use of the rules given in this annex is dependent on the following dimensional and constructional requirements being adhered to:

    NOTE Lateral restraints at the top, or sides, or top and sides, of a wall may need to cope with time dependent movements of the connecting structural parts (e.g. deflection due to creep of a concrete floor) and should be designed accordingly.

  2. The rules given in this clause apply only in circumstances where:
  3. The minimum thickness and limiting dimensions of the wall may be determined from Figure B.1 which provides for the following conditions of lateral restraint to the wall: 26
  4. For walls with openings the minimum thickness and limiting dimensions may also bedetermined from Figure B.1 provided that the type of wall is derived from the basis illustrated in Figure B.2.

    The effect of openings in the wall may be ignored in the following circumstances:

  5. Type a wall with an opening should be considered as a type b wall in which 1 is the greater of 11 and l2 see Figure B.2.
  6. For a type c wall with an opening this annex is not applicable.
  7. For a type d wall with openings this annex is applicable for the left, middle and the right part of the wall if l3 ≥ 2/3 l and l3 ≥ 2/3 h, see Figure B.3.
27

Figure B.1 – Limitation of size thickness ratio of internal walls not subject to vertical load but with limited lateral load

Figure B.1 – Limitation of size thickness ratio of internal walls not subject to vertical load but with limited lateral load

28

Figure B.2 – Type a wall with an opening

Figure B.2 – Type a wall with an opening

Figure B.3 – Type d wall with openings

Figure B.3 – Type d wall with openings

29

Annex C
Simplified calculation method for the design of walls subjected to uniform lateral design load and no vertical loads

(Informative)

  1. The rules given in this clause apply only in circumstances where the dimensions of the wall fulfil the requirements from Annex B.
  2. The minimum thickness, in relation to the length and the height, for walls type a, b and c as described in Annex B,(3), may be determined from Figure C.1 to figure C.9 where:
    t is the thickness of the wall;
    l is the length of the wall;
    h is the height of the wall;
    fxd1 is the design flexural strength of masonry, with the plane of failure parallel to the bed joints;
    fxd2 is the design flexural strength of masonry, with the plane of failure perpendicular to the bed joints;
    PEd is the design value of the lateral load on the wall according to EN 1991.

Figure C.1 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 1,0

Figure C.1 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 1,0

30

Figure C.2 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 0,5

Figure C.2 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 0,5

Figure C.3 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 0,25

Figure C.3 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type a – fxd1 / fxd2 = 0,25

31

Figure C.4 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 1,0

Figure C.4 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 1,0

Figure C.5 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 0,5

Figure C.5 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 0,5

32

Figure C.6 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 0,25

Figure C.6 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type b – fxd1 / fxd2 = 0,25

Figure C.7 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 1,0

Figure C.7 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 1,0

33

Figure C.8 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 1,0

Figure C.8 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 0,5

Figure C.9 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 0,25

Figure C.9 – Thickness and size limitation of non-bearing walls with lateral loading. Wall type c – fxd1 / fxd2 = 0,25

34

Annex D
Simplified method of determining the characteristic strength of masonry

(Normative)

D.1 Characteristic compressive strength

  1. The characteristic compressive strength of masonry may be taken as fk,s, the characteristic compressive strength determined from a simplified method.

NOTE Values of fk,s in N/mm2 to be used in a country may be found in its National Annex. The following tabulated values are recommended; they are derived from clause 3.6.1.2(ii) of EN 1996-1-1:2005.

Clay Units Group 1

fb [N/mm2] General purpose mortar Thin joint Light weight mortar
M2,5 M5 M10 M20 M2,5 M5 M10
2 1,2 1,4 1,4 1,4 1,4 0,6 0,7 0,7
4 1,9 2,4 2,7 2,7 2,4 1,0 1,3 1,5
6 2,5 3,1 3,8 4,1 3,4 1,4 1,7 2,1
8 3,1 3,8 4,7 5,4 4,4 1,7 2,1 2,6
10 3,6 4,5 5,5 6,8 5,3 2,0 2,4 3,0
12 4,1 5,1 6,2 7,7 6,2 2,2 2,8 3,4
16 5,0 6,2 7,6 9,4 7,9 2,8 3,4 4,2
20 5,9 7,3 8,9 11,0 9,6 3,2 4,0 4,9
25 6,9 8,5 10,4 12,9 11,6 3,8 4,6 5,7
30 7,8 9,6 11,9 14,6 13,5 4,3 5,3 6,5
50 11,2 13,8 17,0 20,9 20,9 6,1 7,5 9,3
75 14,9 18,3 22,5 27,7 20,9 8,1 10,0 12,3
35

Clay Units Group 2

fb [N/mm2] General purpose mortar Thin joint Light weight mortar
M2,5 M5 M10 M20 M2,5 M5 M10
2 1,0 1,1 1,1 1,1 1,1 0,5 0,6 0,6
4 1,6 1,9 2,2 2,2 1,8 0,9 1,1 1,2
6 2,1 2,6 3,1 3,3 2,5 1,2 1,4 1,7
8 2,5 3,1 3,8 4,4 3,0 1,4 1,7 2,1
10 3,0 3,7 4,5 5,5 3,5 1,6 2,0 2,5
12 3,4 4,2 5,1 6,3 4,0 1,9 2,3 2,8
16 4,1 5,1 6,3 7,7 4,9 2,3 2,8 3,5
20 4,8 5,9 7,3 9,0 5,7 2,7 3,3 4,1
25 5,6 6,9 8,5 10,5 6,7 3,1 3,9 4,7
30 6,4 7,9 9,7 12,0 7,6 3,6 4,4 5,4
50 9,2 11,3 13,9 17,1 10,8 5,1 6,3 7,7
75 12,2 15,0 18,4 22,7 10,8 6,8 8,3 10,2

Clay Units Group 3 and 4

fb [N/mm2] General purpose mortar Thin joint Light weight mortar
M2,5 M5 M10 M20 Group 3 Group 4 M2,5 M5 M10
2 0,7 0,9 0,9 0,9 0,8 0,6 0,4 0,5 0,5
4 1,2 1,5 1,7 1,7 1,3 1,1 1,7 0,9 1,0
6 1,6 2,0 2,4 2,6 1,8 1,6 0,9 1,1 1,4
8 2,0 2,4 3,0 3,4 2,1 2,0 1,1 1,4 1,7
10 2,3 2,8 3,5 Image4,3 2,5 2,5 1,3 1,6 2,0
12 2,6 3,2 4,0 4,9 2,8 2,9 1,5 1,8 2,3
16 3,2 4,0 4,9 6,0 3,5 3,7 1,8 2,3 2,8
20 3,8 4,6 5,7 7,0 4,1 4,5 2,1 2,6 3,2
25 4,4 5,4 6,6 8,2 4,8 5,4 2,5 3,1 3,8
30 5,0 6,1 7,6 9,3 5,4 6,3 2,8 3,5 4,3
50 7,1 8,8 10,8 13,3 7,7 9,7 4,1 5,0 6,2
75 9,5 11,6 14,3 17,7Image 7,7 9,7 5,4 6,7 8,2
36

Calcium silicate, aggregate concrete and autoclaved aerated concrete units Group 1

fb [N/mm2] General purpose mortar Thin joint Light weight mortar
(not for calcium silicate units)
M2,5 M5 M10 M20 M2,5 M5 M10
2 1,2 1,4 1,4 1,4 1,4 1,0 1,1 1,1
4 1,9 2,4 2,7 2,7 2,6 1,6 1,9 2,2
6 2,5 3,1 3,8 4,1 3,7 2,1 2,6 3,1
8 3,1 4,5 5,5 6,8 5,7 3,0 3,7 4,5
10 3,6 4,5 5,5 6,8 5,7 3,0 3,7 4,5
12 4,1 5,1 6,2 7,7 6,6 3,4 4,2 5,1
16 5,0 6,2 7,6 9,4 8,4 4,1 5,1 6,3
20 5,9 7,3 8,9 11,0 10,2 4,8 5,9 7,3
25 6,9 8,5 10,4 12,9 12,3 5,6 6,9 8,5
30 7,8 9,6 11,9 14,6 14,4 6,4 7,9 9,7
50 11,2 13,8 17,0 20,9 22,2 9,2 11,3 13,9

Calcium silicate and aggregate concrete units Group 2

fb [N/mm2] General purpose mortar Thin joint Light weight mortar
(not for calcium silicate units)
M2,5 M5 M10 M20 M2,5 M5 M10
fb [N/mm2] General purpose mortar Thin joint Light weight mortar
(not for calcium silicate units)
M2,5 M5 M10 M20 M2,5 M5 M10
2 1,0 1,1 1,1 1,1 1,2 1,0 1,1 1,1
4 1,6 1,9 2,2 2,2 2,1 1,6 1,9 2,2
6 2,1 2,6 3,1 3,3 3,0 2,1 2,6 3,1
8 2,5 3,1 3,8 4,4 3,8 2,5 3,1 3,8
10 3,0 3,7 4,5 5,5 4,6 3,0 3,7 4,5
12 3,4 4,2 5,1 6,3 5,4 3,4 4,2 5,1
16 4,1 5,1 6,3 7,7 6,9 4,1 5,1 6,3
20 4,8 5,9 7,3 9,0 8,3 4,8 5,9 7,3
25 5,6 6,9 8,5 10,5 10,0 5,6 6,9 8,5
30 6,4 7,9 9,7 12,0 11,7 6,4 7,9 9,7
50 9,2 11,3 13,9 17,1 18,1 9,2 11,3 13,8
37

Aggregate concrete units Group 3

fb [N/mm2] General purpose mortar Thin joint
M2,5 M5 M10 M20
2 0,9 1,0 1,0 1,0 0,9
4 1,4 1,7 2,0 2,0 1,6
6 1,8 2,3 2,8 3,0 2,3
8 2,3 2,8 3,4 3,9 2,9
10 2,6 3,2 4,0 Image4,9 3,5
12 3,0 3,7 4,5 5,6 4,1
16 3,7 4,5 5,6 6,8 5,3
20 4,3 5,3 6,5 8,0 6,4
25 5,0 6,2 7,6 9,4 7,7
30 5,7 7,0 8,6 10,6 9,0
50 8,1 10,0 12,3 15,2Image 13,9

EN 998-2 gives no limit for the thickness of joints made of thin layer mortar; the values in the above tables are based on the limit on the thickness of bed joints of 0,5 m to 3 mm is to ensure that the thin layer mortar has the enhanced properties required to achieve the given values.

The thickness of the masonry is equal to the width or length of the unit, so that there is no mortar joint parallel to the face of the wall through all or any part of the length of the wall.

The coefficient of variation of the strength of the masonry units is not more than 25 %.

Where action effects are parallel to the direction of the bed joints, the characteristic compressive strength may also be determined from the tables, using the normalised compressive strength of the masonry fb obtained from tests where the direction of application of the load to the test specimen is the same as the direction of the action effect in the masonry, but with the factor, δ as given in EN 772-1:2000, Annex A, not taken to be greater than 1,0. For Group 2 and 3 units, the value of fk obtained from the tables should be multiplied by 0,5.

For masonry made of general purpose mortar where Group 2 and Group 3 aggregate concrete units are used with the vertical cavities filled completely with concrete, the value of fb should be obtained by considering the units to be Group 1 with a compressive strength corresponding to the compressive strength of the units or of the concrete infill, whichever is the lesser.

When the perpend joints are unfilled, the tables may be used, with due consideration being given to any horizontal actions that might be applied to, or be transmitted by, the masonry.

For masonry made with general purpose mortar where there is a mortar joint parallel to the face of the wall through all, or any part, of the length of the wall, the values of fk can be obtained by multiplying the values given in the tables by 0,8.

END of NOTE

38

D.2 Characteristic flexural strengths

  1. The characteristic flexural strengths of masonry may be taken as fxk,1,s and fxk,2,s, the characteristic flexural strengths determined from a simplified method.

    NOTE Values of fxk1,s and fxk2,s to be used in a country may be found in its National Annex. The following values are recommended; they are derived from clause 3.6.3(2) of EN 1996-1-1:2005.

    Masonry unit fxk1,s [N/mnm2]
    General purpose mortar Thin layer mortar Light weight mortar
    <M5 ≥M5
    Clay 0,10 0,10 0,15 0,10
    Calcium silicate 0,05 0,10 0,20 not used
    Aggregate concrete 0,05 0,10 0,20 not used
    Autoclaved aerated concrete 0,05 0,10 0,15 0,10
    Masonry unit fxk2,s [N/mnm2]
    General purpose mortar Thin layer mortar Light weight mortar
    <M5 ≥M5
    Clay 0,20 0,40 0,15 0,10
    Calcium silicate 0,20 0,40 0,30 not used
    Aggregate concrete 0,20 0,40 0,30 not used
    Autoclaved aerated concrete ρ < 400 kg/m3 0,20 0,20 0,20 0,15
    ρ ≥ 400 kg/m3 0,20 0,40 0,30 0,15
    1. Provided that thin layer mortar and light weight mortars are M5, or stronger;
    2. For masonry made with autoclaved aerated concrete units laid in thin layer mortar, fxk1 and fxk2 values may be taken from the tables in this note or from the following equations:

      fxk1,s = 0,035 fb, with filled and unfilled perpend joints;

      fxk2,s = 0,035 fb, with filled perpend joints or 0,025 fb, with unfilled perpend joints.

    END of NOTE

D.3 Characteristic initial shear strength

  1. The characteristic initial shear strength of masonry may be taken as fVko,s, the characteristic initial shear strength determined with a simplified method.
39

NOTE Values of fvko,s, to be used in a country may be found in its National Annex. The following values are recommended, provided that general purpose mortars made in accordance with EN 1996-2 do not contain admixtures or additives; they are derived from Table 3.4 of EN 1996-1-1:2005.

Masonry unit fvko,s [N/mnm2]
General purpose mortar of Strength Class given Thin layer mortar Light weight mortar
Clay Ml – M2 0,10 0,30 0,15
M2,5 – M9 0,20
M10 – M20 0,30
Calcium silicate Ml – M2 0,10 0,40 0,15
M2,5 – M9 0,15
M10 – M20 0,20
Aggregate concrete Ml – M2 0,10 0,30 0,15
Autoclaved aerated M2,5 – M9 0,15
concrete M10 – M20 0,20

END of NOTE

40 41